SPECIFICATIONS
Load Rating: 20 amps @ 230 volts (single phase)
Power Requirement (no load): 3 watts
Surge Let-Through Voltage (6000-volt surge): 0 volts
IEC/EN; 61643-1 Performance Rating: Grade A, Class 1, Mode 1
EMI/RFI Filter, Normal Mode (50-ohm load): 40dB @ 100kHz; 50dB @ 300kHz; 50dB @ 3MHz; 50dB @ 30MHz
EMI/RFI Filter, Common Mode (50-ohm load): 18dB @ 300kHz; 30dB @ 1MHz; 50dB @ 5MHz; 50dB @ 20MHz
Maximum Applied Surge Voltage: 6000 volts*
Maximum Applied Surge Current: Unlimited, due to current limiting*
Maximum Applied Surge Energy: Unlimited, due to current limiting*
Endurance (C62.41-1991 Category B3 pulses): 1 kV>500,000; 3kV>10,000; 6 kV>1000
Dimensions: 25.4 x 20.3 x 10.7 cm (10.0" H x 8.0" W x 4.0" D)
Weight: 4.5Kg (10 lbs)
Temperature Range: 5° to 35° C
Humidity Range: 5% to 95% R.H., non-condensing
*1.2 x 50µs pulse, industry standard combination wave surge, as per IEEE C62.41 |
FEATURES
- Magnetic shielding steel enclosure
- Advanced Series Mode® Surge Elimination
- Advanced impedance Tolerant® EMI/RFI filtering
- Thermal circuit breaker overload protection
- Self-test circuit with visual indicator
- 10-year warranty
TECHNICAL DESCRIPTION
The SXN1230 shall be housed in a magnetic shielding NEMA steel enclosure for interior installations. It shall operate from 230 volts AC and have a barrier strip accessible through knock-outs in the enclosure for hardwiring power input and output connections. Overall dimensions shall be 10.0" H x 8.0" W x 4.0" D. Weight shall be 4.5 Kg / 10.0 pounds. The SXN1230 shall have a load rating of 20 amps at 230 volts, a self-test circuit with visual indicator and provide EMI/RFI filtering. It shall meet Grade A, Class 1, Mode 1 guidelines for power line surge suppressors and withstand at least 1000 occurrences of surge pulse voltages up to 6000 volts. The SXN1230 shall be tested and certified to IEC/EN 61643-1. |