SPECIFICATIONS
Load Rating: 16 amps @ 230 volts
Power Requirement (no load): 3 watts
Surge Let-Through Voltage (6000-volt surge): 0 volts
IEC/EN: 61643-1 Performance Rating: Grade A, Class 1, Mode 1
EMI/RFI Filter, Normal Mode (50-ohm load): 40dB @ 100kHz; 50dB @ 300kHz; 50dB @ 3MHz; 50dB @ 30MHz
EMI/RFI Filter, Common Mode (50-ohm load): 18dB @ 300kHz: 30dB @ 1MHz; 50dB @ 5MHz; 50dB @ 20MHz
Maximum Applied Surge Voltage: 6000 volts*
Maximum Applied Surge Current: Unlimited, due to current limiting*
Maximum Applied Surge Energy: Unlimited, due to current limiting*
Endurance (C62.41-1991 Category B3 pulses): 1 kV>500,000;3kV>10,000; 6kV>1000
Dimensions: 1.75"H x 19"W x 10.5"D (4.5 x 48.3 x 26.7cm)
Weight: 11 lbs (5.0 kg)
Temperature Range: 5° to 35° C
Humidity Range: 5% to 95% R.H., non-condensing
* 1.2 x 50 µs pulse, industry standard combination wave surge, as per IEEE C62.41 |
FEATURES
- Magnetic shielding steel enclosure
- 9' power cord
- 10 earthed AC receptacles on rear panel (8 switched, 2 always on)
- 1 earthed AC receptacle on front panel
- Advanced Series Mode® Surge Elimination
- Advanced Impedance Tolerant® EMI/RFI filtering
- Thermal circuit breaker overload protection
- Self-test circuit with visual indicator
- 10-year warranty
- Engineered in the U.S.A.
TECHNICAL DESCRIPTION
The SX1216i shall be a one-rack-space unit in a magnetic shielding steel enclosure. It shall operate from 230 volts AC and have a 9-foot power cord. There shall be 10 earthed AC receptacles on the back panel, with 6 switched and 2 always on. In addition, there shall be a single always-on receptacle on the front panel Overall dimensions shall be 4.5cm 5Kg 11 Lbs).
The SX1216i shall have a load rating of 16 amps at 230 volts, a self-test circuit with visual indicator, and provide EMI/RFI filtering. It shall meet Grade A, Class 1, Mode 1 guidelines for powerline surge suppressors and withstand at least 1000 occurrences of surge pulse voltages up to 6000 volts. |